Rule Fire protection directive 19-15 Sprinkler systems
Protected extent: full protection, partial protection over whole compartments, annexes and canopies
VKF-19-15-006
pragmaticBIM.ch/vkf-19-15-006
Sprinkler systems should be designed as full protection and cover entire buildings and installations, except expressly exempted rooms separated with fire resistance. Partial protection covers at least one whole fire compartment.
Description
Annexes and canopies are included if they are used for storage or for parking vehicles and containers and their separation from adjoining uses has insufficient fire resistance. Where sprinklers are technically impossible, for example in high rooms, alternative measures apply in agreement with the authority. Not yet checkable: the model holds no sprinkler system with protected extent, control station and water supply.
Source
VKF-Brandschutzrichtlinie 19-15 Sprinkleranlagen (2015) (p. 5)
More rules for Fire protection directive 19-15 Sprinkler systems
-
VKF-19-15-007
Permitted exceptions from sprinkler protection
Sprinklers can be omitted, among others, in wet rooms without combustible stock, technical rooms with low fire hazard as a separate compartment, small rooms up to 4 m², cold rooms up to 50, 200 or 600 m² depending on insulation and separation, crawl spaces without fire load, vertical escape routes separated with...
-
VKF-19-15-008
Water unsuitable: substitute measures with equivalent protection in the fire protection concept
Where water is not a suitable extinguishing agent, for example for silos with swelling contents, industrial furnaces and baths with increased hazard, substances that form combustible gases with water, or other endangered areas, substitute measures with equivalent protection are taken in agreement with the fire...
-
VKF-19-15-009
Sprinkler control room: separate compartment of at least EI 30, between 1st upper floor and 1st basement, secured access
Sprinkler control rooms are located in separate fire compartments with the fire resistance of the use-related compartmentation, at least EI 30, with EI 30 doors.