Rule Fire protection directive 19-15 Sprinkler systems
Rooms with large occupancy: sprinklers on request
VKF-19-15-005
pragmaticBIM.ch/vkf-19-15-005
In buildings and installations with rooms of large occupancy the fire protection authority can require sprinkler systems. Not yet checkable: the model does not show use, occupancy, number of storeys and compartment size per fire compartment.
Source
VKF-Brandschutzrichtlinie 19-15 Sprinkleranlagen (2015) (p. 4)
More rules for Fire protection directive 19-15 Sprinkler systems
-
VKF-19-15-006
Protected extent: full protection, partial protection over whole compartments, annexes and canopies
Sprinkler systems should be designed as full protection and cover entire buildings and installations, except expressly exempted rooms separated with fire resistance. Partial protection covers at least one whole fire compartment.
-
VKF-19-15-007
Permitted exceptions from sprinkler protection
Sprinklers can be omitted, among others, in wet rooms without combustible stock, technical rooms with low fire hazard as a separate compartment, small rooms up to 4 m², cold rooms up to 50, 200 or 600 m² depending on insulation and separation, crawl spaces without fire load, vertical escape routes separated with...
-
VKF-19-15-008
Water unsuitable: substitute measures with equivalent protection in the fire protection concept
Where water is not a suitable extinguishing agent, for example for silos with swelling contents, industrial furnaces and baths with increased hazard, substances that form combustible gases with water, or other endangered areas, substitute measures with equivalent protection are taken in agreement with the fire...