Rule Fire protection directive 19-15 Sprinkler systems
Car parks and garages: sprinklers from 4,800, 2,400 or 9,600 m² and for compact parking above 50 vehicles
VKF-19-15-004
pragmaticBIM.ch/vkf-19-15-004
Underground garages need sprinklers from 4,800 m² compartment area per storey, multi-storey ones with open connections from 2,400 m². Closed above-ground garages need them from 4,800 m², partly open ones (enclosure with 25 % non-closable openings) from 9,600 m² per storey.
Description
Installations with mechanical compact parking for more than 50 vehicles always need a sprinkler system. Not yet checkable: the model does not show use, occupancy, number of storeys and compartment size per fire compartment.
Source
VKF-Brandschutzrichtlinie 19-15 Sprinkleranlagen (2015) (p. 4)
More rules for Fire protection directive 19-15 Sprinkler systems
-
VKF-19-15-005
Rooms with large occupancy: sprinklers on request
In buildings and installations with rooms of large occupancy the fire protection authority can require sprinkler systems. Not yet checkable: the model does not show use, occupancy, number of storeys and compartment size per fire compartment.
-
VKF-19-15-006
Protected extent: full protection, partial protection over whole compartments, annexes and canopies
Sprinkler systems should be designed as full protection and cover entire buildings and installations, except expressly exempted rooms separated with fire resistance. Partial protection covers at least one whole fire compartment.
-
VKF-19-15-007
Permitted exceptions from sprinkler protection
Sprinklers can be omitted, among others, in wet rooms without combustible stock, technical rooms with low fire hazard as a separate compartment, small rooms up to 4 m², cold rooms up to 50, 200 or 600 m² depending on insulation and separation, crawl spaces without fire load, vertical escape routes separated with...