Rule Fire protection directive 19-15 Sprinkler systems
Shops above 2,400 m² compartment area: sprinklers including adjoining storage and service rooms
VKF-19-15-003
pragmaticBIM.ch/vkf-19-15-003
Shops with more than 2,400 m² compartment area, including the adjoining storage and service rooms, are protected by sprinkler systems and supplemented with manual call points. Not yet checkable: the model does not show use, occupancy, number of storeys and compartment size per fire compartment.
Source
VKF-Brandschutzrichtlinie 19-15 Sprinkleranlagen (2015) (p. 4)
More rules for Fire protection directive 19-15 Sprinkler systems
-
VKF-19-15-004
Car parks and garages: sprinklers from 4,800, 2,400 or 9,600 m² and for compact parking above 50 vehicles
Underground garages need sprinklers from 4,800 m² compartment area per storey, multi-storey ones with open connections from 2,400 m². Closed above-ground garages need them from 4,800 m², partly open ones (enclosure with 25 % non-closable openings) from 9,600 m² per storey.
-
VKF-19-15-005
Rooms with large occupancy: sprinklers on request
In buildings and installations with rooms of large occupancy the fire protection authority can require sprinkler systems. Not yet checkable: the model does not show use, occupancy, number of storeys and compartment size per fire compartment.
-
VKF-19-15-006
Protected extent: full protection, partial protection over whole compartments, annexes and canopies
Sprinkler systems should be designed as full protection and cover entire buildings and installations, except expressly exempted rooms separated with fire resistance. Partial protection covers at least one whole fire compartment.