Rule Fire protection directive 19-15 Sprinkler systems
Industry, commerce, offices: sprinklers for exceeded compartments, fast fires, hazardous substances or high fire load
VKF-19-15-002
pragmaticBIM.ch/vkf-19-15-002
For industrial, commercial and office buildings the fire protection authority can require a sprinkler system if the permitted compartment sizes are exceeded and the system makes sense for the use, if fast-developing fires are expected, the ignition hazard is high, hazardous substances are handled or stored, or the...
Description
For industrial, commercial and office buildings the fire protection authority can require a sprinkler system if the permitted compartment sizes are exceeded and the system makes sense for the use, if fast-developing fires are expected, the ignition hazard is high, hazardous substances are handled or stored, or the fire load is very high. Not yet checkable: the model does not show use, occupancy, number of storeys and compartment size per fire compartment.
Source
VKF-Brandschutzrichtlinie 19-15 Sprinkleranlagen (2015) (p. 4)
More rules for Fire protection directive 19-15 Sprinkler systems
-
VKF-19-15-003
Shops above 2,400 m² compartment area: sprinklers including adjoining storage and service rooms
Shops with more than 2,400 m² compartment area, including the adjoining storage and service rooms, are protected by sprinkler systems and supplemented with manual call points. Not yet checkable: the model does not show use, occupancy, number of storeys and compartment size per fire compartment.
-
VKF-19-15-004
Car parks and garages: sprinklers from 4,800, 2,400 or 9,600 m² and for compact parking above 50 vehicles
Underground garages need sprinklers from 4,800 m² compartment area per storey, multi-storey ones with open connections from 2,400 m². Closed above-ground garages need them from 4,800 m², partly open ones (enclosure with 25 % non-closable openings) from 9,600 m² per storey.
-
VKF-19-15-005
Rooms with large occupancy: sprinklers on request
In buildings and installations with rooms of large occupancy the fire protection authority can require sprinkler systems. Not yet checkable: the model does not show use, occupancy, number of storeys and compartment size per fire compartment.