Rule Fire protection directive 15-15 Fire safety distances, load-bearing structures, fire compartments
Installation shafts: separate flue systems and ducts with enhanced requirements
VKF-15-15-017
pragmaticBIM.ch/vkf-15-15-017
Flue systems, ventilation ducts with enhanced fire protection requirements and similar lines are separated from each other and from the other installations in the same shaft with 30 minutes of fire resistance made of RF1 materials, e.g. fire protection boards.
Description
Not yet checkable: the model shows neither the contents of a shaft nor the separating layers between the lines.
Source
VKF-Brandschutzrichtlinie 15-15 Brandschutzabstände, Tragwerke, Brandabschnitte (2015) (p. 10)
More rules for Fire protection directive 15-15 Fire safety distances, load-bearing structures, fire compartments
-
VKF-15-15-018
Housing: dwellings as separate fire compartments
Dwellings are built as separate fire compartments. For single-family houses including their basements and an associated granny flat, no fire resistance is required of structure, walls and floors.
-
VKF-15-15-019
School buildings: fire compartment at most 3600 m², special rooms separate
School operations and associated uses, as well as the gymnasium with its ancillary rooms, may each be combined in one fire compartment. Without special proof the contiguous compartment area is at most 3600 m²; it includes all storeys connected without fire resistance.
-
VKF-15-15-020
Accommodation: guest rooms and technical rooms as fire compartments
In accommodation facilities, guest, inmate, patient and staff rooms, operational technical rooms, examination, treatment and laboratory areas, and technical rooms are each built as fire compartments. Not yet checkable: the model does not identify fire compartments.