Rule Fire protection directive 15-15 Fire safety distances, load-bearing structures, fire compartments
Installation shafts: horizontal subdivision at every storey
VKF-15-15-016
pragmaticBIM.ch/vkf-15-15-016
In installation shafts that are closed at the top, the recesses for lines are closed with RF1 materials at every storey.
Description
The subdivision can be omitted if there is a smoke and heat vent of 5 % of the shaft cross-section at the top leading to the open air that is permanently open or can be opened from a safe place, if the shaft is filled without voids with RF1 materials (in low and medium-height buildings without special installations non-melting RF2 materials suffice), or if only lines made of RF1 materials are present. Not yet checkable: shaft closures, fillings and line materials are not represented in the model.
Source
VKF-Brandschutzrichtlinie 15-15 Brandschutzabstände, Tragwerke, Brandabschnitte (2015) (p. 10)
More rules for Fire protection directive 15-15 Fire safety distances, load-bearing structures, fire compartments
-
VKF-15-15-017
Installation shafts: separate flue systems and ducts with enhanced requirements
Flue systems, ventilation ducts with enhanced fire protection requirements and similar lines are separated from each other and from the other installations in the same shaft with 30 minutes of fire resistance made of RF1 materials, e.g. fire protection boards.
-
VKF-15-15-018
Housing: dwellings as separate fire compartments
Dwellings are built as separate fire compartments. For single-family houses including their basements and an associated granny flat, no fire resistance is required of structure, walls and floors.
-
VKF-15-15-019
School buildings: fire compartment at most 3600 m², special rooms separate
School operations and associated uses, as well as the gymnasium with its ancillary rooms, may each be combined in one fire compartment. Without special proof the contiguous compartment area is at most 3600 m²; it includes all storeys connected without fire resistance.