Rule Fire protection directive 15-15 Fire safety distances, load-bearing structures, fire compartments
Office buildings: fire compartment at most 3600 m²
VKF-15-15-010
pragmaticBIM.ch/vkf-15-15-010
In office buildings a fire compartment covers at most 3600 m² without special proof. All storeys connected without fire resistance count together.
Description
Uses belonging to the office (e.g. meeting rooms, archives, server rooms, kitchenettes) may share the compartment. Not yet checkable: fire compartments are not stored as zones in the model.
Source
VKF-Brandschutzrichtlinie 15-15 Brandschutzabstände, Tragwerke, Brandabschnitte (2015) (p. 14)
More rules for Fire protection directive 15-15 Fire safety distances, load-bearing structures, fire compartments
-
VKF-15-15-011
Penetrations through compartment components: firestop of at least 30 minutes
Openings and service penetrations in walls and floors that form fire compartments are closed with fire resistance; the firestop holds for at least 30 minutes. Allowing for thermal expansion, the recess is either filled tightly with RF1 materials or closed with a VKF-recognized firestop system rated EI 30.
-
VKF-15-15-012
Pipes through compartment components: recognized firestop system
Where pipes pass through components that form fire compartments, a VKF-recognized firestop system is used, e.g. a fire collar.
-
VKF-15-15-013
Combustible pipe insulation interrupted at the penetration
Combustible thermal insulation on services is interrupted with RF1 material where the service passes through a wall or floor that forms a fire compartment. For tested and recognized components the VKF recognition applies.