Rule Fire protection directive 25-15 Ventilation systems
Hangers and thermal insulation of ventilation ducts
VKF-25-15-007
pragmaticBIM.ch/vkf-25-15-007
Hangers and fixings of RF1 ducts are also RF1 (except vibration dampers and the like) and hold the duct securely for the required fire resistance duration. Thermal insulation of RF1 ducts is RF1; outdoor-air ducts may use at least RF3 (cr) if covered on all sides with at least 0.5 mm of RF1.
Description
Insulation of combustible ducts may be at least RF3. Not yet checkable: hangers and insulation layers are not held in the model as separate elements with reaction to fire.
Source
VKF-Brandschutzrichtlinie 25-15 Lufttechnische Anlagen (2015) (p. 6)
More rules for Fire protection directive 25-15 Ventilation systems
-
VKF-25-15-008
Ducts without openings through other sections: EI 30 or fire dampers
Ventilation ducts that run without openings through other fire or ventilation sections, or whose outlets are on the storey above or below, are built or clad with EI 30. In airlocks and vertical escape routes the fire resistance of the use-related compartmentation applies, at least EI 30.
-
VKF-25-15-009
Inspection and cleaning openings; no foreign installations in ventilation ducts
Ventilation ducts are arranged and fitted with openings so that they can be inspected and cleaned. Only parts that serve the system may be installed in ventilation ducts and air-carrying shafts (except ventilation ceilings and floors).
-
VKF-25-15-010
Duct penetration through compartment-forming components: firestop EI 30 or RF1 filling
The recess between the ventilation duct and the compartment-forming component is, allowing for thermal expansion, either filled tightly with RF1 materials (e.g. mortar, plaster) or closed with a firestop system that reaches EI 30 in compartment-forming walls and floors.