Rule Fire protection directive 25-15 Ventilation systems

Ventilation ducts of RF1, exceptions at least RF3

VKF-25-15-006 pragmaticBIM.ch/vkf-25-15-006

Ventilation ducts, ventilation ceilings and floors are made of RF1 materials. At least RF3 is enough within the fire compartment of ventilation sections in office, school and dwelling units, for ventilation ceilings and floors within one compartment, for ducts cast in concrete and for earth registers.

Description

Flexible ducts are at least RF3 and allowed without length limit within one fire compartment as long as they only ventilate it; RF1 flexible ducts are limited to 2 m for equipment connections in the equipment room, RF3 ones to 2 m for air outlets and 4 m for local extraction. Not yet checkable: ducts carry no reaction to fire, and ventilation sections and flexible lengths are not modelled.

Source

VKF-Brandschutzrichtlinie 25-15 Lufttechnische Anlagen (2015) (p. 6)