Rule Fire protection directive 25-15 Ventilation systems
Smoke trigger device at the extract connection of systems serving several ventilation sections
VKF-25-15-005
pragmaticBIM.ch/vkf-25-15-005
Systems that serve several ventilation sections (fire compartments combined for ventilation purposes) have a smoke trigger device at the extract connection. When it responds, it switches the system off and closes the fire dampers.
Description
This can be omitted where the rooms are monitored by a fire detection system and the ventilation system has a fire-case control. Not yet checkable: the model does not link smoke trigger devices, ventilation sections and the fire detection system.
Source
VKF-Brandschutzrichtlinie 25-15 Lufttechnische Anlagen (2015) (p. 5)
More rules for Fire protection directive 25-15 Ventilation systems
-
VKF-25-15-006
Ventilation ducts of RF1, exceptions at least RF3
Ventilation ducts, ventilation ceilings and floors are made of RF1 materials. At least RF3 is enough within the fire compartment of ventilation sections in office, school and dwelling units, for ventilation ceilings and floors within one compartment, for ducts cast in concrete and for earth registers.
-
VKF-25-15-007
Hangers and thermal insulation of ventilation ducts
Hangers and fixings of RF1 ducts are also RF1 (except vibration dampers and the like) and hold the duct securely for the required fire resistance duration. Thermal insulation of RF1 ducts is RF1; outdoor-air ducts may use at least RF3 (cr) if covered on all sides with at least 0.5 mm of RF1.
-
VKF-25-15-008
Ducts without openings through other sections: EI 30 or fire dampers
Ventilation ducts that run without openings through other fire or ventilation sections, or whose outlets are on the storey above or below, are built or clad with EI 30. In airlocks and vertical escape routes the fire resistance of the use-related compartmentation applies, at least EI 30.