Rule Fire protection directive 21-15 Smoke and heat exhaust systems
Smoke and heat exhaust by use, position and fire-compartment area
VKF-21-15-001
pragmaticBIM.ch/vkf-21-15-001
Depending on occupancy, number of storeys, construction type, position and use, fire compartments must be equipped with an adequately sized smoke and heat exhaust system.
Description
A table sets area or occupancy thresholds for industrial, commercial and storage rooms, offices, car parks, rooms with large occupancy, sales rooms, atria and high-bay warehouses, above which the system becomes necessary; fire-extinguishing systems raise the thresholds. Open car parks above ground need no system. Not yet checkable: the model holds no smoke and heat exhaust system and no assignment of one to fire compartments.
Source
VKF-Brandschutzrichtlinie 21-15 Rauch- und Wärmeabzugsanlagen (2015) (p. 5)
More rules for Fire protection directive 21-15 Smoke and heat exhaust systems
-
VKF-21-15-002
Systems without performance proof: system type and sizing by use
For systems without performance proof the directive sets, per use, position and area, which system type is permitted: smoke clearance with fire-brigade fans, mechanical or natural systems. Sizing follows air-change rates by room height or supply and exhaust areas as a percentage of the compartment area.
-
VKF-21-15-003
Vertical escape routes: exhaust opening at the top, directly outdoors
Vertical escape routes get exhaust openings at the top leading directly outdoors: in low and medium-height buildings for accommodation, large occupancy and shops, in medium-height buildings for residential, office, industrial, commercial and school buildings and car parks, unless every storey has ventilation sashes...
-
VKF-21-15-004
Stairwell exhaust opening: 0.5 m² free, operable from the entrance level
The free geometric ventilation area of the exhaust opening at a vertical escape route is at least 0.5 m². It can be put into operation from the entrance level, and it stays operational during a power failure.