Rule Fire protection directive 20-15 Fire alarm systems
Specialist firm, documentation, switch-off, project, acceptance, inspection and review after 15 years
VKF-20-15-015
pragmaticBIM.ch/vkf-20-15-015
Fire alarm systems are planned, installed and maintained by VKF-recognised specialist firms, with components covered by a declaration of performance or VKF technical information. Orientation plans at the fire-brigade access and a logbook at the control panel are kept.
Description
Systems are in principle not switched off; longer interruptions must be reported and decommissioning needs approval. Projects (over 10 detectors or 600 m²) are submitted before execution, the systems are accepted, inspected periodically and reviewed after 15 years; owners or operators keep them ready for operation.
Source
VKF-Brandschutzrichtlinie 20-15 Brandmeldeanlagen (2015) (p. 9)
More rules for Fire protection directive 20-15 Fire alarm systems
-
VKF-20-15-001
Fire alarm system by occupancy and use, special buildings on request
Depending on occupancy and use, buildings, installations or fire compartments are equipped with an adequately sized fire alarm system. It can be required for early alerting of rescue forces, for early activation of fire protection and building services systems, and in large and complex buildings.
-
VKF-20-15-002
Industry, commerce, offices: monitoring when compartments are exceeded, smouldering fires or ban on water
For industrial, commercial and office buildings the fire protection authority can require monitoring if the permitted compartment sizes are exceeded and the system makes sense for the current use, if slowly developing fires such as smouldering fires are expected, or if water must not be used as extinguishing agent.
-
VKF-20-15-003
Accommodation: fire alarm system with full monitoring by category, number of storeys and persons
In accommodation of category a a fire alarm system with full monitoring is required.