Rule Fire protection directive 18-15 Fire-extinguishing equipment
Extinguishers: walking line to the nearest device at most 40 m
VKF-18-15-007
pragmaticBIM.ch/vkf-18-15-007
Extinguishers are distributed so that a fire can be fought at any point; the walking line to the nearest extinguisher is at most 40 m. In areas with particular fire hazards, additional devices are installed at suitable places.
Description
Not yet checkable: the model shows extinguishers and hose reels only as a device with location, without extinguishing agent, rating or walking distance.
Source
VKF-Brandschutzrichtlinie 18-15 Löscheinrichtungen (2015) (p. 5)
More rules for Fire protection directive 18-15 Fire-extinguishing equipment
-
VKF-18-15-008
Hose reels: valve of at least DN 32, form-stable hose up to 40 m with nozzle
A hose reel consists of a shut-off valve with a connection of at least DN 32, a movable connection to the swivelling reel, and a form-stable rubber hose with a shut-off nozzle for jet and spray. In special cases, such as agricultural buildings, an equivalent device may replace the reel.
-
VKF-18-15-009
Hose-reel supply line: at least DN 32 in RF1, 3 bar static pressure, 16 l/min
The supply line to a hose reel is at least DN 32 and made of materials of reaction-to-fire group RF1; combustible pipes are laid under plaster with fire resistance EI 30 or equally protected. A static pressure of 3 bar prevails at the hose reel and the flow is at least 16 l/min.
-
VKF-18-15-010
High-rise buildings: fire-fighting risers with interior hydrants (at least DN 80) or pressure-boosting connection
High-rise buildings are equipped with fire-fighting installations such as wet or dry risers, hose reels with interior hydrants (supply line at least DN 80) or pressure-boosting connections. The requirements are set case by case with the fire protection authority.