Rule Fire protection directive 18-15 Fire-extinguishing equipment
Hose-reel supply line: at least DN 32 in RF1, 3 bar static pressure, 16 l/min
VKF-18-15-009
pragmaticBIM.ch/vkf-18-15-009
The supply line to a hose reel is at least DN 32 and made of materials of reaction-to-fire group RF1; combustible pipes are laid under plaster with fire resistance EI 30 or equally protected. A static pressure of 3 bar prevails at the hose reel and the flow is at least 16 l/min.
Description
Not yet checkable: the model does not show nominal size, material, reaction to fire, static pressure and flow of the fire-fighting pipe.
Source
VKF-Brandschutzrichtlinie 18-15 Löscheinrichtungen (2015) (p. 5)
More rules for Fire protection directive 18-15 Fire-extinguishing equipment
-
VKF-18-15-010
High-rise buildings: fire-fighting risers with interior hydrants (at least DN 80) or pressure-boosting connection
High-rise buildings are equipped with fire-fighting installations such as wet or dry risers, hose reels with interior hydrants (supply line at least DN 80) or pressure-boosting connections. The requirements are set case by case with the fire protection authority.
-
VKF-18-15-011
Dry and cooling extinguishing systems: scope, subdivision, sizing and pressure relief
The scope of special dry and cooling extinguishing systems is limited to individual rooms, areas and equipment. Arrangement and sizing ensure effective cooling or extinguishing effect; pressure-relief openings are installed and large areas are subdivided.
-
VKF-18-15-012
Safety of people with dry extinguishing systems: pre-warning, self-closing doors, danger sign
Dry extinguishing systems get warning and delay devices if flooding can endanger people. The pre-warning time between the alarm signal and release of the agent is long enough to leave the flooding zone safely from any point.