Rule Fire protection directive 17-15 Escape route marking, safety lighting, safety power supply
Accommodation: illuminated escape signs on safety lighting and safety lighting
VKF-17-15-002
pragmaticBIM.ch/vkf-17-15-002
In accommodation facilities, exits and escape routes are marked with escape signs on safety lighting, and safety lighting is installed in the escape routes. For remote accommodation facilities (e.g. mountain huts) the fire authority decides whether it is needed.
Description
Not yet checkable: the model shows neither the type of facility nor the lighting type of the escape signs.
Source
VKF-Brandschutzrichtlinie 17-15 Kennzeichnung von Fluchtwegen, Sicherheitsbeleuchtung, Sicherheitsstromversorgung (2015) (p. 4)
More rules for Fire protection directive 17-15 Escape route marking, safety lighting, safety power supply
-
VKF-17-15-003
Car parks: safety lighting also in the room, e.g. in driving lanes
In car parks, exits and escape routes are marked with escape signs on safety lighting and the escape routes are fitted with safety lighting. The escape routes within the parking area itself, for example along the driving lanes, also get safety lighting.
-
VKF-17-15-004
Rooms with large occupancy, shops: signs lit continuously
In rooms with large occupancy and in shops, exits and escape routes are marked with escape signs on safety lighting. Their lighting stays on as long as people are in the room.
-
VKF-17-15-005
Escape signs: direction indicators, visibility and height across the escape direction
The escape direction is marked with direction indicators if it is not immediately obvious or if people unfamiliar with the premises are present, for example at changes of direction. Exits that are not immediately recognizable or are used only in emergencies are marked.