Room type Data centre

Chiller room

RT-TE-04 pragmaticBIM.ch/rt-te-04

Room for chillers and cooling plant.

Room name code

RN-09-10-04 Chiller room

Standard values

Interior spaces

Attribute Value Unit
PredefinedType SPACE
IsExternal Pset_SpaceCommon FALSE
LongName Chiller room
Reference Pset_SpaceCommon FF
NetPlannedArea ePset_SpaceRequirement 40 m²
FloorCovering Pset_SpaceCoveringRequirements Beton
WallCovering Pset_SpaceCoveringRequirements Beton roh
CeilingCovering Pset_SpaceCoveringRequirements Metal grid ceiling
VibrationRequirements ePset_SpaceRequirement ISO Workshop
InteriorOrExteriorSpace INTERNAL
DesignAreaLoad ePset_SpaceRequirement 5 kN/m²
DesignPointLoad ePset_SpaceRequirement 4 kN
SecurityLevel ePset_Space Restricted
PeakOccupancy ePset_SpaceRequirement 2 Personen
DailyOperatingHours ePset_SpaceRequirement 1 h/Tag
OutdoorAirFlowRate ePset_SpaceRequirement 60 m³/h

Equipment

Chiller 1 (1-3)
Pump 2 (1-4)
Socket outlet
  • preferred · elevation
  • required · not in clearance of · access
  • preferred · next to · access (≤ 1 m)
min. 1, 1 per 10 m² net floor area
Light switch
  • required · next to · access (≤ 0.3 m)
  • required · elevation
1

Openings

More room types of this use

Contact

abstract ag

Imprint · Picassoplatz 4, 4052 Basel