Server room
RT-TE-07
pragmaticBIM.ch/rt-te-07
Room for IT and network equipment.
Room name code
RN-09-20-02 Server room
Standard values
| Attribute | Value | Unit |
|---|---|---|
| PredefinedType | SPACE | |
| IsExternal Pset_SpaceCommon | FALSE | |
| LongName | Server room | |
| Reference Pset_SpaceCommon | FF | |
| NetPlannedArea ePset_SpaceRequirement | 20 | m² |
| FloorCovering Pset_SpaceCoveringRequirements | Beton | |
| WallCovering Pset_SpaceCoveringRequirements | Beton roh | |
| CeilingCovering Pset_SpaceCoveringRequirements | Metal grid ceiling | |
| VibrationRequirements ePset_SpaceRequirement | ISO Workshop | |
| InteriorOrExteriorSpace | INTERNAL | |
| DesignAreaLoad ePset_SpaceRequirement | 5 | kN/m² |
| DesignPointLoad ePset_SpaceRequirement | 4 | kN |
| SecurityLevel ePset_Space | Restricted | |
| RelativeHumidityMin ePset_SpaceRequirement | 40 | % |
| RelativeHumidityMax ePset_SpaceRequirement | 60 | % |
| PeakOccupancy ePset_SpaceRequirement | 2 | Personen |
| DailyOperatingHours ePset_SpaceRequirement | 1 | h/Tag |
| OutdoorAirFlowRate ePset_SpaceRequirement | 60 | m³/h |
Equipment
| Server rack | min. 2, 1 per 2.5 m² net floor area |
| UPS unit | 1 (0-2) |
| Distribution board | 1 |
Socket outlet
|
min. 1, 1 per 10 m² net floor area |
Light switch
|
1 |