Rule Fire protection directive 18-15 Fire-extinguishing equipment
Dry and cooling extinguishing systems: scope, subdivision, sizing and pressure relief
VKF-18-15-011
pragmaticBIM.ch/vkf-18-15-011
The scope of special dry and cooling extinguishing systems is limited to individual rooms, areas and equipment. Arrangement and sizing ensure effective cooling or extinguishing effect; pressure-relief openings are installed and large areas are subdivided.
Description
Agent quantity, pipe and distribution system secure concentration, flooding and exposure time; flooding zones are kept as small as possible and sized individually, with the largest demand governing. Not yet checkable: the model holds no dry or cooling extinguishing system with flooding zones, warning and release devices.
Source
VKF-Brandschutzrichtlinie 18-15 Löscheinrichtungen (2015) (p. 5)
More rules for Fire protection directive 18-15 Fire-extinguishing equipment
-
VKF-18-15-012
Safety of people with dry extinguishing systems: pre-warning, self-closing doors, danger sign
Dry extinguishing systems get warning and delay devices if flooding can endanger people. The pre-warning time between the alarm signal and release of the agent is long enough to leave the flooding zone safely from any point.
-
VKF-18-15-013
Release of special extinguishing systems automatic or manual, with signal and internal alarm
Cooling or extinguishing agent can be released automatically or by hand. Systems with automatic release can also be operated by hand.
-
VKF-18-15-014
Instruction, project, acceptance, periodic inspection and maintenance
Persons responsible for a business instruct staff in the handling of extinguishers and special systems. Projects for dry and cooling extinguishing systems are submitted for approval before construction starts when required, and the systems are accepted and inspected periodically.