Rule Fire protection directive 18-15 Fire-extinguishing equipment
Extinguishers in vertical escape routes only under conditions, hose reels not in safety stairwells
VKF-18-15-005
pragmaticBIM.ch/vkf-18-15-005
Extinguishers may stand in vertical escape routes if there are no fire doors between vertical and horizontal escape routes, for example in office and school buildings up to 900 m² gross floor area, or if several rooms are accessed directly from the vertical escape route. Hose reels in safety stairwells are not allowed.
Description
Not yet checkable: the model shows extinguishers and hose reels only as a device with location, without extinguishing agent, rating or walking distance.
Source
VKF-Brandschutzrichtlinie 18-15 Löscheinrichtungen (2015) (p. 5)
More rules for Fire protection directive 18-15 Fire-extinguishing equipment
-
VKF-18-15-006
Uniform arrangement, open placement or cabinet without weakening the fire resistance
With similar floor plans and room layouts, extinguishers are arranged as uniformly as possible. They stand in the open or in separate cabinets; recessed cabinets must not weaken the fire resistance of compartment-forming walls.
-
VKF-18-15-007
Extinguishers: walking line to the nearest device at most 40 m
Extinguishers are distributed so that a fire can be fought at any point; the walking line to the nearest extinguisher is at most 40 m. In areas with particular fire hazards, additional devices are installed at suitable places.
-
VKF-18-15-008
Hose reels: valve of at least DN 32, form-stable hose up to 40 m with nozzle
A hose reel consists of a shut-off valve with a connection of at least DN 32, a movable connection to the swivelling reel, and a form-stable rubber hose with a shut-off nozzle for jet and spray. In special cases, such as agricultural buildings, an equivalent device may replace the reel.