Room type Healthcare

Imaging room

RT-HE-07 pragmaticBIM.ch/rt-he-07

Room for diagnostic imaging.

Room name code

RN-05-30-01 Imaging room

Standard values

Interior spaces

Attribute Value Unit
PredefinedType SPACE
IsExternal Pset_SpaceCommon FALSE
LongName Imaging room
Reference Pset_SpaceCommon HNF
NetPlannedArea ePset_SpaceRequirement 40 m²
FloorCovering Pset_SpaceCoveringRequirements Epoxidharzbelag
WallCovering Pset_SpaceCoveringRequirements fugenloser Belag
CeilingCovering Pset_SpaceCoveringRequirements Metal grid ceiling
VibrationRequirements ePset_SpaceRequirement ISO Operating Theatre (OT)
InteriorOrExteriorSpace INTERNAL
DesignAreaLoad ePset_SpaceRequirement 3 kN/m²
DesignPointLoad ePset_SpaceRequirement 2 kN
SecurityLevel ePset_Space Internal
WinterTemperatureMin ePset_SpaceRequirement 20 °C
WinterTemperatureMax ePset_SpaceRequirement 24 °C
SummerTemperatureMin ePset_SpaceRequirement 22 °C
SummerTemperatureMax ePset_SpaceRequirement 26 °C
RequiredIlluminance ePset_SpaceRequirement 1000 lx
PeakOccupancy ePset_SpaceRequirement 8 Personen
DailyOperatingHours ePset_SpaceRequirement 10 h/Tag
OutdoorAirFlowRate ePset_SpaceRequirement 240 m³/h

Equipment

Imaging device space 1
Socket outlet
  • preferred · elevation
  • required · not in clearance of · access
min. 1, 1 per 10 m² net floor area
Light switch
  • required · next to · access (≤ 0.3 m)
  • required · elevation
1

Openings

More room types of this use

Contact

abstract ag

Imprint · Picassoplatz 4, 4052 Basel