Cellar compartment
RT-WH-21
pragmaticBIM.ch/rt-wh-21
Assigned cellar storage compartment for a dwelling.
Room name code
RN-01-20-08 Cellar compartment
Standard values
| Attribute | Value | Unit |
|---|---|---|
| PredefinedType | SPACE | |
| IsExternal Pset_SpaceCommon | FALSE | |
| LongName | Cellar compartment | |
| Reference Pset_SpaceCommon | HNF | |
| NetPlannedArea ePset_SpaceRequirement | 4 | m² |
| FloorCovering Pset_SpaceCoveringRequirements | Beton | |
| WallCovering Pset_SpaceCoveringRequirements | Beton roh | |
| CeilingCovering Pset_SpaceCoveringRequirements | Other / unknown ceiling covering | |
| VibrationRequirements ePset_SpaceRequirement | ISO Residential (Night) | |
| InteriorOrExteriorSpace | INTERNAL | |
| DesignAreaLoad ePset_SpaceRequirement | 2 | kN/m² |
| DesignPointLoad ePset_SpaceRequirement | 2 | kN |
| SecurityLevel ePset_Space | Internal | |
| WinterTemperatureMin ePset_SpaceRequirement | 20 | °C |
| WinterTemperatureMax ePset_SpaceRequirement | 24 | °C |
| SummerTemperatureMin ePset_SpaceRequirement | 22 | °C |
| SummerTemperatureMax ePset_SpaceRequirement | 26 | °C |
| RequiredIlluminance ePset_SpaceRequirement | 100 | lx |
| PeakOccupancy ePset_SpaceRequirement | 1 | Personen |
| DailyOperatingHours ePset_SpaceRequirement | 1 | h/Tag |
| OutdoorAirFlowRate ePset_SpaceRequirement | 30 | m³/h |
Equipment
| Shelf | 2 (0-4) |
Socket outlet
|
min. 1, 1 per 10 m² net floor area |
Light switch
|
1 |