Room type

Nurses station

RT-HE-10 pragmaticBIM.ch/rt-he-10

Central nursing and monitoring workspace.

Room name code

RN-05-30-04 Nurses station

Standard values

Interior spaces

Attribute Value Unit
PredefinedType SPACE
IsExternal Pset_SpaceCommon FALSE
LongName Nurses station
Reference Pset_SpaceCommon HNF
NetPlannedArea ePset_SpaceRequirement 20 m²
FloorCovering Pset_SpaceCoveringRequirements Linoleum
WallCovering Pset_SpaceCoveringRequirements Anstrich
CeilingCovering Pset_SpaceCoveringRequirements Mineral-fibre acoustic ceiling
VibrationRequirements ePset_SpaceRequirement ISO Office
InteriorOrExteriorSpace INTERNAL
DesignAreaLoad ePset_SpaceRequirement 3 kN/m²
DesignPointLoad ePset_SpaceRequirement 2 kN
SecurityLevel ePset_Space Internal
WinterTemperatureMin ePset_SpaceRequirement 20 °C
WinterTemperatureMax ePset_SpaceRequirement 24 °C
SummerTemperatureMin ePset_SpaceRequirement 22 °C
SummerTemperatureMax ePset_SpaceRequirement 26 °C
RequiredIlluminance ePset_SpaceRequirement 500 lx
PeakOccupancy ePset_SpaceRequirement 8 Personen
DailyOperatingHours ePset_SpaceRequirement 10 h/Tag
OutdoorAirFlowRate ePset_SpaceRequirement 240 m³/h

Equipment

Office workstation min. 1, 1 per 8 m² net floor area
Worktop 1
Washbasin 1
Socket outlet
  • preferred · elevation
  • required · not in clearance of · access
  • preferred · next to · working (≤ 0.5 m)
min. 1, 1 per 10 m² net floor area
Light switch
  • required · next to · access (≤ 0.3 m)
  • required · elevation
1