Bildgebungsraum
RT-HE-07
pragmaticBIM.ch/rt-he-07
Raum für diagnostische Bildgebung.
Raumname-Code
RN-05-30-01 Bildgebungsraum
Standardwerte
| Attribut | Wert | Einheit |
|---|---|---|
| PredefinedType | SPACE | |
| IsExternal Pset_SpaceCommon | FALSE | |
| LongName | Bildgebungsraum | |
| Reference Pset_SpaceCommon | HNF | |
| FloorCovering Pset_SpaceCoveringRequirements | Epoxidharzbelag | |
| WallCovering Pset_SpaceCoveringRequirements | fugenloser Belag | |
| CeilingCovering Pset_SpaceCoveringRequirements | Metallraster-Decke | |
| VibrationRequirements ePset_SpaceRequirement | ISO Operating Theatre (OT) | |
| InteriorOrExteriorSpace | INTERNAL | |
| DesignAreaLoad ePset_SpaceRequirement | 3 | kN/m² |
| DesignPointLoad ePset_SpaceRequirement | 2 | kN |
| SecurityLevel ePset_Space | Intern | |
| WinterTemperatureMin ePset_SpaceRequirement | 20 | °C |
| WinterTemperatureMax ePset_SpaceRequirement | 24 | °C |
| SummerTemperatureMin ePset_SpaceRequirement | 22 | °C |
| SummerTemperatureMax ePset_SpaceRequirement | 26 | °C |
| RequiredIlluminance ePset_SpaceRequirement | 1000 | lx |
| PeakOccupancy ePset_SpaceRequirement | 8 | Personen |
| DailyOperatingHours ePset_SpaceRequirement | 10 | h/Tag |
| OutdoorAirFlowRate ePset_SpaceRequirement | 240 | m³/h |