Bettenaufzug
RT-CI-07
pragmaticBIM.ch/rt-ci-07
Aufzug für den Transport von Patientinnen und Patienten im Bett.
Raumname-Code
RN-03-20-05 Bettenaufzug
Standardwerte
| Attribut | Wert | Einheit |
|---|---|---|
| PredefinedType | SPACE | |
| IsExternal Pset_SpaceCommon | FALSE | |
| LongName | Bettenaufzug | |
| Reference Pset_SpaceCommon | VF | |
| FloorCovering Pset_SpaceCoveringRequirements | PVC | |
| WallCovering Pset_SpaceCoveringRequirements | Anstrich | |
| CeilingCovering Pset_SpaceCoveringRequirements | Metallpaneel-Decke | |
| VibrationRequirements ePset_SpaceRequirement | ISO Office | |
| InteriorOrExteriorSpace | INTERNAL | |
| DesignAreaLoad ePset_SpaceRequirement | 5 | kN/m² |
| DesignPointLoad ePset_SpaceRequirement | 4 | kN |
| SecurityLevel ePset_Space | Eingeschränkt | |
| WinterTemperatureMin ePset_SpaceRequirement | 18 | °C |
| WinterTemperatureMax ePset_SpaceRequirement | 22 | °C |
| SummerTemperatureMin ePset_SpaceRequirement | 20 | °C |
| SummerTemperatureMax ePset_SpaceRequirement | 26 | °C |
| RequiredIlluminance ePset_SpaceRequirement | 200 | lx |
| PeakOccupancy ePset_SpaceRequirement | 10 | Personen |
| DailyOperatingHours ePset_SpaceRequirement | 12 | h/Tag |
| OutdoorAirFlowRate ePset_SpaceRequirement | 300 | m³/h |