Raumtyp Gesundheit

Schleuse

RT-CI-02 pragmaticBIM.ch/rt-ci-02

Geschlossene Schleuse für kontrollierten Übergang zwischen Bereichen.

Raumname-Code

RN-03-10-05 Schleuse

Standardwerte

Innenräume

Attribut Wert Einheit
PredefinedType SPACE
IsExternal Pset_SpaceCommon FALSE
LongName Schleuse
Reference Pset_SpaceCommon VF
FloorCovering Pset_SpaceCoveringRequirements Plattenbelag
WallCovering Pset_SpaceCoveringRequirements Anstrich
CeilingCovering Pset_SpaceCoveringRequirements Metallpaneel-Decke
VibrationRequirements ePset_SpaceRequirement ISO Office
InteriorOrExteriorSpace INTERNAL
DesignAreaLoad ePset_SpaceRequirement 4 kN/m²
DesignPointLoad ePset_SpaceRequirement 3 kN
SecurityLevel ePset_Space Intern
WinterTemperatureMin ePset_SpaceRequirement 16 °C
WinterTemperatureMax ePset_SpaceRequirement 20 °C
SummerTemperatureMin ePset_SpaceRequirement 20 °C
SummerTemperatureMax ePset_SpaceRequirement 28 °C
RequiredIlluminance ePset_SpaceRequirement 100 lx
PeakOccupancy ePset_SpaceRequirement 2 Personen
DailyOperatingHours ePset_SpaceRequirement 12 h/Tag
OutdoorAirFlowRate ePset_SpaceRequirement 60 m³/h