Interior spaces
SPACE-INT
Links the room programme, area verification, and discipline planning so that use, sizing, and technical requirements can be coordinated for each space.
Description
- Usable interior spaces modelled as continuous volumes.
- Room use is carried in LongName; Name may carry the room number.
Modelling guidelines
- Model as a volume with the space tool, storey by storey.
- From top of finished floor to underside of the structural ceiling - not a suspended ceiling. This allows other trades to reuse the space, for example to assign building services to it.
- No overlaps or duplicates.
- Fill every void in the building with a space object.
- For rental-area or energy-reference-area calculations, choose and agree one of three approaches in advance: create a separate disposable model used only for the evaluation, with the required space definitions; adjust the calculation using suitable factors; or knowingly accept the remaining inaccuracy.
Discussion point
- For discipline planning, defining the space volume from the top of the structural floor slab to the underside of the structural slab above would be beneficial. This would allow installations within the floor build-up to be assigned unambiguously to the space. However, many authoring tools do not support this approach reliably, so it is not generally recommended here.
FinishFloorHeightorFloorCoveringThicknesscould additionally document the level difference.
Attributes
| Name | Description | Unit |
|---|---|---|
| Name |
Unique technical room number for planning. It provides discipline designers with a stable ID for linking their data permanently to the space and identifying significant changes quickly. It should stay stable as long as:
Do not use for signage - signage room numbers change often and belong in SignageRoomNumber. |
|
| PredefinedType |
Marks the object as a space. Allowed values
Note
|
|
| InteriorOrExteriorSpace |
Marks the space as interior. Allowed values
Note
|
|
| LongName |
Room use for interior spaces according to the brief. Allowed values
|
|
|
Reference
Pset_SpaceCommon |
Area class of the space according to SIA 416 or SIA D0165. Allowed values
|
|
|
IsExternal
Pset_SpaceCommon |
Marks an interior space. Allowed values
|
|
|
NetPlannedArea
Pset_SpaceCommon |
Ordered target net area of the space. |
m² |
|
SignageRoomNumber
ePset_Space |
Room number for wayfinding signage (labelling, orientation). Separate from the technical planning room number (Name), because signage numbers often change and are therefore not stable identifiers for planning and operation. |
|
|
FloorCovering
Pset_SpaceCoveringRequirements |
Interior floor covering type for early planning - as a space property only, without a modelled floor build-up. Allowed values
|
|
|
TotalHeatLoss
Pset_SpaceThermalDesign |
Heating load for each space at design conditions as the basis for sizing heat emission. Note
|
W |
|
DesignAreaLoad
ePset_SpaceRequirement |
Agreed design area load for the usage agreement. |
kN/m² |
|
DesignPointLoad
ePset_SpaceRequirement |
Agreed design point load for the usage agreement. |
kN |
|
VibrationRequirements
ePset_SpaceRequirement |
Agreed vibration requirements for the usage agreement according to ISO vibration criteria and Vibration Criterion (VC) per IEST. Allowed values
|
|
|
DesignAreaLoadActual
ePset_Space |
Verified actual area load for comparison with the usage agreement. |
kN/m² |
|
DesignPointLoadActual
ePset_Space |
Verified actual point load for comparison with the usage agreement. |
kN |
|
VibrationRequirementsActual
ePset_Space |
Verified actual vibration class for comparison with the usage agreement according to ISO vibration criteria and Vibration Criterion (VC) per IEST. Allowed values
|
|
|
WinterTemperatureMin
ePset_SpaceRequirement |
Agreed minimum room temperature in winter. |
°C |
|
WinterTemperatureMax
ePset_SpaceRequirement |
Agreed maximum room temperature in winter. |
°C |
|
SummerTemperatureMin
ePset_SpaceRequirement |
Agreed minimum room temperature in summer. |
°C |
|
SummerTemperatureMax
ePset_SpaceRequirement |
Agreed maximum room temperature in summer. |
°C |
|
RelativeHumidityMin
ePset_SpaceRequirement |
Agreed minimum relative humidity in the space. |
% |
|
RelativeHumidityMax
ePset_SpaceRequirement |
Agreed maximum relative humidity in the space. |
% |
|
OutdoorAirFlowRate
ePset_SpaceRequirement |
Agreed outdoor airflow rate for the space. |
m³/h |
|
PeakOccupancy
ePset_SpaceRequirement |
Agreed maximum number of people present at the same time. |
Personen |
|
DailyOperatingHours
ePset_SpaceRequirement |
Agreed daily operating duration of the space. |
h/Tag |
|
RequiredIlluminance
ePset_SpaceRequirement |
Agreed average illuminance in the space. |
lx |
|
WinterTemperatureMinActual
ePset_Space |
Verified actual minimum room temperature in winter. |
°C |
|
WinterTemperatureMaxActual
ePset_Space |
Verified actual maximum room temperature in winter. |
°C |
|
SummerTemperatureMinActual
ePset_Space |
Verified actual minimum room temperature in summer. |
°C |
|
SummerTemperatureMaxActual
ePset_Space |
Verified actual maximum room temperature in summer. |
°C |
|
RelativeHumidityMinActual
ePset_Space |
Verified actual minimum relative humidity in the space. |
% |
|
RelativeHumidityMaxActual
ePset_Space |
Verified actual maximum relative humidity in the space. |
% |
|
OutdoorAirFlowRateActual
ePset_Space |
Verified actual outdoor airflow rate for the space. |
m³/h |
|
PeakOccupancyActual
ePset_Space |
Verified actual maximum number of people present at the same time. |
Personen |
|
DailyOperatingHoursActual
ePset_Space |
Verified actual daily operating duration of the space. |
h/Tag |
|
RequiredIlluminanceActual
ePset_Space |
Verified actual average illuminance in the space. |
lx |
|
Checkliste
ePset_Space |
Free-text description of fit-out work in the room including sequence - so contractors on site can see what needs to be done. |
|
|
UsageUnitReference
ePset_Space |
Stable reference of the usage unit to which the space belongs, for example an apartment, office unit, or commercial unit. It should where possible be populated using an algorithm based on the space's geometric position within the corresponding gross volume. Note
|
|
|
FireCompartmentReference
ePset_Space |
Stable reference of the fire compartment to which the space belongs according to the fire-protection concept. |
|
|
SecurityZoneReference
ePset_Space |
Stable reference of the security zone to which the space belongs according to the security concept. |
|
|
SecurityLevel
ePset_Space |
Security level of the space according to the security concept. Allowed values
|
|
|
ProtectionGoal
ePset_Space |
Protection goal of the space according to the security concept. Allowed values
|
|
|
NetFloorArea
Qto_SpaceBaseQuantities |
Net floor area of the modelled space. |
m² |
|
NetPerimeter
Qto_SpaceBaseQuantities |
Net perimeter length at floor level of the modelled space - excluding segments at virtual boundaries and openings; may include the perimeter of fixed fittings such as columns. |
m |
|
NetVolume
Qto_SpaceBaseQuantities |
Net volume of the modelled space. |
m³ |
|
Height
Qto_SpaceBaseQuantities |
Height of the modelled space volume. |
m |
|
FinishCeilingHeight
Qto_SpaceBaseQuantities |
Suspended ceiling height - clear height from top of finished floor to underside of the suspended ceiling. Note
|
m |
|
WallCovering
Pset_SpaceCoveringRequirements |
Wall finish quality for space-based tendering - without a separately modelled wall covering. Allowed values
|
|
|
GrossWallArea
Qto_SpaceBaseQuantities |
Gross area of the wall surfaces bounding the space before deducting openings. |
m² |
|
NetWallArea
Qto_SpaceBaseQuantities |
Net area of the wall surfaces bounding the space after deducting modelled openings. |
m² |
|
HandicapAccessible
Pset_SpaceCommon |
Marks whether the space is accessible and included in the coloured accessible route. Allowed values
|