Interior spaces

SPACE-INT

Links the room programme, area verification, and discipline planning so that use, sizing, and technical requirements can be coordinated for each space.

Description

  • Usable interior spaces modelled as continuous volumes.
  • Room use is carried in LongName; Name may carry the room number.

Modelling guidelines

  • Model as a volume with the space tool, storey by storey.
  • From top of finished floor to underside of the structural ceiling - not a suspended ceiling. This allows other trades to reuse the space, for example to assign building services to it.
  • No overlaps or duplicates.
  • Fill every void in the building with a space object.
  • For rental-area or energy-reference-area calculations, choose and agree one of three approaches in advance: create a separate disposable model used only for the evaluation, with the required space definitions; adjust the calculation using suitable factors; or knowingly accept the remaining inaccuracy.

Discussion point

  • For discipline planning, defining the space volume from the top of the structural floor slab to the underside of the structural slab above would be beneficial. This would allow installations within the floor build-up to be assigned unambiguously to the space. However, many authoring tools do not support this approach reliably, so it is not generally recommended here. FinishFloorHeight or FloorCoveringThickness could additionally document the level difference.

Attributes

Name Description Unit
Name

Unique technical room number for planning. It provides discipline designers with a stable ID for linking their data permanently to the space and identifying significant changes quickly. It should stay stable as long as:

  • the room size does not change substantially (e.g. from 12 m² office to 25 m² open-plan office)
  • the function does not change substantially (e.g. from office to meeting room)
  • and the orientation does not change (e.g. from south to east facing)

Do not use for signage - signage room numbers change often and belong in SignageRoomNumber.

PredefinedType

Marks the object as a space.

Allowed values

  • SPACE - space

Note

  • The also permitted values INTERNAL and EXTERNAL conflate space type and location and have been deprecated since IFC4.3_ADD2. Therefore, use SPACE now and specify interior or exterior status using IsExternal.
InteriorOrExteriorSpace

Marks the space as interior.

Allowed values

  • INTERNAL - interior space

Note

  • Additional IFC2x3 classification; interior status is specified across all versions using IsExternal.
LongName

Room use for interior spaces according to the brief.

Allowed values

Reference

Pset_SpaceCommon

Area class of the space according to SIA 416 or SIA D0165.

Allowed values

IsExternal

Pset_SpaceCommon

Marks an interior space.

Allowed values

  • FALSE - interior space
NetPlannedArea

Pset_SpaceCommon

Ordered target net area of the space.

m²
SignageRoomNumber

ePset_Space

Room number for wayfinding signage (labelling, orientation). Separate from the technical planning room number (Name), because signage numbers often change and are therefore not stable identifiers for planning and operation.

FloorCovering

Pset_SpaceCoveringRequirements

Interior floor covering type for early planning - as a space property only, without a modelled floor build-up.

Allowed values

TotalHeatLoss

Pset_SpaceThermalDesign

Heating load for each space at design conditions as the basis for sizing heat emission.

Note

  • Result of the heating-load calculation; provide the power in watts.
W
DesignAreaLoad

ePset_SpaceRequirement

Agreed design area load for the usage agreement.

kN/m²
DesignPointLoad

ePset_SpaceRequirement

Agreed design point load for the usage agreement.

kN
VibrationRequirements

ePset_SpaceRequirement

Agreed vibration requirements for the usage agreement according to ISO vibration criteria and Vibration Criterion (VC) per IEST.

Allowed values

  • ISO Workshop - 800 µm/s (32'000 µin/s): workshops, coarse manufacturing areas, machine protection zones
  • ISO Office - 400 µm/s (16'000 µin/s): offices, control rooms, general administrative areas
  • ISO Residential (Night) - 200 µm/s (8'000 µin/s): residential areas (night), light PC workplaces, microscopes <40×
  • ISO Operating Theatre (OT) - 100 µm/s (4'000 µin/s): baseline (Base Curve): operating theatres, general laboratories, microscopes up to 100×
  • VC-A - Vibration Criterion A per IEST
  • VC-B - Vibration Criterion B per IEST
  • VC-C - Vibration Criterion C per IEST
  • VC-D - Vibration Criterion D per IEST
  • VC-E - Vibration Criterion E per IEST
DesignAreaLoadActual

ePset_Space

Verified actual area load for comparison with the usage agreement.

kN/m²
DesignPointLoadActual

ePset_Space

Verified actual point load for comparison with the usage agreement.

kN
VibrationRequirementsActual

ePset_Space

Verified actual vibration class for comparison with the usage agreement according to ISO vibration criteria and Vibration Criterion (VC) per IEST.

Allowed values

  • ISO Workshop - 800 µm/s (32'000 µin/s): workshops, coarse manufacturing areas, machine protection zones
  • ISO Office - 400 µm/s (16'000 µin/s): offices, control rooms, general administrative areas
  • ISO Residential (Night) - 200 µm/s (8'000 µin/s): residential areas (night), light PC workplaces, microscopes <40×
  • ISO Operating Theatre (OT) - 100 µm/s (4'000 µin/s): baseline (Base Curve): operating theatres, general laboratories, microscopes up to 100×
  • VC-A - Vibration Criterion A per IEST
  • VC-B - Vibration Criterion B per IEST
  • VC-C - Vibration Criterion C per IEST
  • VC-D - Vibration Criterion D per IEST
  • VC-E - Vibration Criterion E per IEST
WinterTemperatureMin

ePset_SpaceRequirement

Agreed minimum room temperature in winter.

°C
WinterTemperatureMax

ePset_SpaceRequirement

Agreed maximum room temperature in winter.

°C
SummerTemperatureMin

ePset_SpaceRequirement

Agreed minimum room temperature in summer.

°C
SummerTemperatureMax

ePset_SpaceRequirement

Agreed maximum room temperature in summer.

°C
RelativeHumidityMin

ePset_SpaceRequirement

Agreed minimum relative humidity in the space.

%
RelativeHumidityMax

ePset_SpaceRequirement

Agreed maximum relative humidity in the space.

%
OutdoorAirFlowRate

ePset_SpaceRequirement

Agreed outdoor airflow rate for the space.

m³/h
PeakOccupancy

ePset_SpaceRequirement

Agreed maximum number of people present at the same time.

Personen
DailyOperatingHours

ePset_SpaceRequirement

Agreed daily operating duration of the space.

h/Tag
RequiredIlluminance

ePset_SpaceRequirement

Agreed average illuminance in the space.

lx
WinterTemperatureMinActual

ePset_Space

Verified actual minimum room temperature in winter.

°C
WinterTemperatureMaxActual

ePset_Space

Verified actual maximum room temperature in winter.

°C
SummerTemperatureMinActual

ePset_Space

Verified actual minimum room temperature in summer.

°C
SummerTemperatureMaxActual

ePset_Space

Verified actual maximum room temperature in summer.

°C
RelativeHumidityMinActual

ePset_Space

Verified actual minimum relative humidity in the space.

%
RelativeHumidityMaxActual

ePset_Space

Verified actual maximum relative humidity in the space.

%
OutdoorAirFlowRateActual

ePset_Space

Verified actual outdoor airflow rate for the space.

m³/h
PeakOccupancyActual

ePset_Space

Verified actual maximum number of people present at the same time.

Personen
DailyOperatingHoursActual

ePset_Space

Verified actual daily operating duration of the space.

h/Tag
RequiredIlluminanceActual

ePset_Space

Verified actual average illuminance in the space.

lx
Checkliste

ePset_Space

Free-text description of fit-out work in the room including sequence - so contractors on site can see what needs to be done.

UsageUnitReference

ePset_Space

Stable reference of the usage unit to which the space belongs, for example an apartment, office unit, or commercial unit. It should where possible be populated using an algorithm based on the space's geometric position within the corresponding gross volume.

Note

  • Alternatively, the spaces of a usage unit can be grouped using IfcZone.
FireCompartmentReference

ePset_Space

Stable reference of the fire compartment to which the space belongs according to the fire-protection concept.

SecurityZoneReference

ePset_Space

Stable reference of the security zone to which the space belongs according to the security concept.

SecurityLevel

ePset_Space

Security level of the space according to the security concept.

Allowed values

  • Public
  • Internal
  • Restricted
  • High security
ProtectionGoal

ePset_Space

Protection goal of the space according to the security concept.

Allowed values

  • Burglary
  • Sabotage
  • Espionage
  • Vandalism
NetFloorArea

Qto_SpaceBaseQuantities

Net floor area of the modelled space.

m²
NetPerimeter

Qto_SpaceBaseQuantities

Net perimeter length at floor level of the modelled space - excluding segments at virtual boundaries and openings; may include the perimeter of fixed fittings such as columns.

m
NetVolume

Qto_SpaceBaseQuantities

Net volume of the modelled space.

m³
Height

Qto_SpaceBaseQuantities

Height of the modelled space volume.

m
FinishCeilingHeight

Qto_SpaceBaseQuantities

Suspended ceiling height - clear height from top of finished floor to underside of the suspended ceiling.

Note

  • For an uneven suspended ceiling, pick the worst case for use: the deepest underside (smallest clear height).
m
WallCovering

Pset_SpaceCoveringRequirements

Wall finish quality for space-based tendering - without a separately modelled wall covering.

Allowed values

  • See the Wall surface quality value list.
GrossWallArea

Qto_SpaceBaseQuantities

Gross area of the wall surfaces bounding the space before deducting openings.

m²
NetWallArea

Qto_SpaceBaseQuantities

Net area of the wall surfaces bounding the space after deducting modelled openings.

m²
HandicapAccessible

Pset_SpaceCommon

Marks whether the space is accessible and included in the coloured accessible route.

Allowed values

  • TRUE - accessible
  • FALSE - not verified as accessible