Locale server
RT-TE-07
pragmaticBIM.ch/rt-te-07
Locale per la tecnica informatica e di rete.
Codice nome locale
RN-09-20-02 Locale server
Valori standard
| Attributo | Valore | Unità |
|---|---|---|
| PredefinedType | SPACE | |
| IsExternal Pset_SpaceCommon | FALSE | |
| LongName | Locale server | |
| Reference Pset_SpaceCommon | FF | |
| NetPlannedArea ePset_SpaceRequirement | 20 | m² |
| FloorCovering Pset_SpaceCoveringRequirements | Beton | |
| WallCovering Pset_SpaceCoveringRequirements | Beton roh | |
| CeilingCovering Pset_SpaceCoveringRequirements | Metal grid ceiling | |
| VibrationRequirements ePset_SpaceRequirement | ISO Workshop | |
| InteriorOrExteriorSpace | INTERNAL | |
| DesignAreaLoad ePset_SpaceRequirement | 5 | kN/m² |
| DesignPointLoad ePset_SpaceRequirement | 4 | kN |
| SecurityLevel ePset_Space | Ristretto | |
| RelativeHumidityMin ePset_SpaceRequirement | 40 | % |
| RelativeHumidityMax ePset_SpaceRequirement | 60 | % |
| PeakOccupancy ePset_SpaceRequirement | 2 | Personen |
| DailyOperatingHours ePset_SpaceRequirement | 1 | h/Tag |
| OutdoorAirFlowRate ePset_SpaceRequirement | 60 | m³/h |
Attrezzatura
| Armadio server | min. 2, 1 per 2.5 m² di superficie netta di piano |
| Gruppo di continuità | 1 (0-2) |
| Quadro secondario | 1 |
Presa
|
min. 1, 1 per 10 m² di superficie netta di piano |
Interruttore della luce
|
1 |
Aperture
| Porta a battente interna oppure Porta a due ante interna oppure Porta esterna | 1 |
Altri tipi di locale di questa destinazione d'uso
-
RT-TE-10
Locale comunicazioni
Locale per gli impianti di telecomunicazione e di corrente debole.
-
RT-WH-39
Condotto rifiuti
Condotto verticale per convogliare i rifiuti domestici verso un punto di raccolta centrale.
-
RT-WH-40
Area esterna di raccolta rifiuti
Area esterna per raccogliere e conferire i rifiuti domestici in sacchi.