Local serveurs
RT-TE-07
pragmaticBIM.ch/rt-te-07
Local pour la technique informatique et de réseau.
Code du nom de local
RN-09-20-02 Local serveurs
Valeurs standard
| Attribut | Valeur | Unité |
|---|---|---|
| PredefinedType | SPACE | |
| IsExternal Pset_SpaceCommon | FALSE | |
| LongName | Local serveurs | |
| Reference Pset_SpaceCommon | FF | |
| NetPlannedArea ePset_SpaceRequirement | 20 | m² |
| FloorCovering Pset_SpaceCoveringRequirements | Beton | |
| WallCovering Pset_SpaceCoveringRequirements | Beton roh | |
| CeilingCovering Pset_SpaceCoveringRequirements | Metal grid ceiling | |
| VibrationRequirements ePset_SpaceRequirement | ISO Workshop | |
| InteriorOrExteriorSpace | INTERNAL | |
| DesignAreaLoad ePset_SpaceRequirement | 5 | kN/m² |
| DesignPointLoad ePset_SpaceRequirement | 4 | kN |
| SecurityLevel ePset_Space | Restreint | |
| RelativeHumidityMin ePset_SpaceRequirement | 40 | % |
| RelativeHumidityMax ePset_SpaceRequirement | 60 | % |
| PeakOccupancy ePset_SpaceRequirement | 2 | Personen |
| DailyOperatingHours ePset_SpaceRequirement | 1 | h/Tag |
| OutdoorAirFlowRate ePset_SpaceRequirement | 60 | m³/h |
Équipement
| Armoire serveur | min. 2, 1 pour 2.5 m² de surface nette de plancher |
| Alimentation sans interruption | 1 (0-2) |
| Tableau divisionnaire | 1 |
Prise
|
min. 1, 1 pour 10 m² de surface nette de plancher |
Interrupteur d'éclairage
|
1 |
Ouvertures
Autres types de locaux de cette affectation
-
RT-TE-10
Local de communication
Local pour les installations de télécommunication et de courant faible.
-
RT-WH-39
Gaine vide-ordures
Gaine verticale destinée à acheminer les déchets ménagers vers un point de collecte central.
-
RT-WH-40
Aire extérieure de collecte des déchets
Aire extérieure destinée à collecter et présenter les déchets ménagers en sacs.