Type de local Laboratoire et recherche
Local électrique
RT-TE-06
pragmaticBIM.ch/rt-te-06
Local pour la distribution électrique.
Code du nom de local
RN-09-20-01 Local électrique
Valeurs standard
| Attribut | Valeur | Unité |
|---|---|---|
| PredefinedType | SPACE | |
| IsExternal Pset_SpaceCommon | FALSE | |
| LongName | Local électrique | |
| Reference Pset_SpaceCommon | FF | |
| NetPlannedArea ePset_SpaceRequirement | 15 | m² |
| FloorCovering Pset_SpaceCoveringRequirements | Beton | |
| WallCovering Pset_SpaceCoveringRequirements | Beton roh | |
| CeilingCovering Pset_SpaceCoveringRequirements | Metal grid ceiling | |
| VibrationRequirements ePset_SpaceRequirement | ISO Workshop | |
| InteriorOrExteriorSpace | INTERNAL | |
| DesignAreaLoad ePset_SpaceRequirement | 5 | kN/m² |
| DesignPointLoad ePset_SpaceRequirement | 4 | kN |
| SecurityLevel ePset_Space | Restreint | |
| PeakOccupancy ePset_SpaceRequirement | 2 | Personen |
| DailyOperatingHours ePset_SpaceRequirement | 1 | h/Tag |
| OutdoorAirFlowRate ePset_SpaceRequirement | 60 | m³/h |
Équipement
| Tableau principal | 1 |
| Tableau divisionnaire | 1 (0-4) |
Prise
|
min. 1, 1 pour 10 m² de surface nette de plancher |
Interrupteur d'éclairage
|
1 |