Type de local

Local sprinklers

RT-TE-05 pragmaticBIM.ch/rt-te-05

Local pour les installations sprinkler et d'extinction.

Code du nom de local

RN-09-10-05 Local sprinklers

Valeurs standard

Espaces intérieurs

Attribut Valeur Unité
PredefinedType SPACE
IsExternal Pset_SpaceCommon FALSE
LongName Local sprinklers
Reference Pset_SpaceCommon FF
NetPlannedArea ePset_SpaceRequirement 20 m²
FloorCovering Pset_SpaceCoveringRequirements Beton
WallCovering Pset_SpaceCoveringRequirements Beton roh
CeilingCovering Pset_SpaceCoveringRequirements Metal grid ceiling
VibrationRequirements ePset_SpaceRequirement ISO Workshop
InteriorOrExteriorSpace INTERNAL
DesignAreaLoad ePset_SpaceRequirement 5 kN/m²
DesignPointLoad ePset_SpaceRequirement 4 kN
SecurityLevel ePset_Space Restreint
PeakOccupancy ePset_SpaceRequirement 2 Personen
DailyOperatingHours ePset_SpaceRequirement 1 h/Tag
OutdoorAirFlowRate ePset_SpaceRequirement 60 m³/h

Équipement

Pompe 2 (1-2)
Tableau divisionnaire 1
Prise
  • préféré · elevation
  • requis · hors dégagement de · accès
  • préféré · à côté de · accès (≤ 1 m)
min. 1, 1 pour 10 m² de surface nette de plancher
Interrupteur d'éclairage
  • requis · à côté de · accès (≤ 0.3 m)
  • requis · elevation
1

Ouvertures

Contact

abstract ag

Imprint · Picassoplatz 4, 4052 Basel