Type de local Santé

Ascenseur pour lits

RT-CI-07 pragmaticBIM.ch/rt-ci-07

Ascenseur pour le transport de patients alités.

Code du nom de local

RN-03-20-05 Ascenseur pour lits

Valeurs standard

Espaces intérieurs

Attribut Valeur Unité
PredefinedType SPACE
IsExternal Pset_SpaceCommon FALSE
LongName Ascenseur pour lits
Reference Pset_SpaceCommon VF
NetPlannedArea ePset_SpaceRequirement 6 m²
FloorCovering Pset_SpaceCoveringRequirements PVC
WallCovering Pset_SpaceCoveringRequirements Anstrich
CeilingCovering Pset_SpaceCoveringRequirements Metal panel ceiling
VibrationRequirements ePset_SpaceRequirement ISO Office
InteriorOrExteriorSpace INTERNAL
DesignAreaLoad ePset_SpaceRequirement 5 kN/m²
DesignPointLoad ePset_SpaceRequirement 4 kN
SecurityLevel ePset_Space Restreint
WinterTemperatureMin ePset_SpaceRequirement 18 °C
WinterTemperatureMax ePset_SpaceRequirement 22 °C
SummerTemperatureMin ePset_SpaceRequirement 20 °C
SummerTemperatureMax ePset_SpaceRequirement 26 °C
RequiredIlluminance ePset_SpaceRequirement 200 lx
PeakOccupancy ePset_SpaceRequirement 10 Personen
DailyOperatingHours ePset_SpaceRequirement 12 h/Tag
OutdoorAirFlowRate ePset_SpaceRequirement 300 m³/h