Type de local Transport de voyageurs
Hall des guichets
RT-CI-05
pragmaticBIM.ch/rt-ci-05
Hall avec guichets et distributeurs de billets pour le transport de voyageurs.
Code du nom de local
RN-03-30-02 Hall des guichets
Valeurs standard
| Attribut | Valeur | Unité |
|---|---|---|
| PredefinedType | SPACE | |
| IsExternal Pset_SpaceCommon | FALSE | |
| LongName | Hall des guichets | |
| Reference Pset_SpaceCommon | VF | |
| NetPlannedArea ePset_SpaceRequirement | 150 | m² |
| FloorCovering Pset_SpaceCoveringRequirements | Naturstein | |
| WallCovering Pset_SpaceCoveringRequirements | Anstrich | |
| CeilingCovering Pset_SpaceCoveringRequirements | Metal panel ceiling | |
| VibrationRequirements ePset_SpaceRequirement | ISO Office | |
| InteriorOrExteriorSpace | INTERNAL | |
| DesignAreaLoad ePset_SpaceRequirement | 5 | kN/m² |
| DesignPointLoad ePset_SpaceRequirement | 4 | kN |
| SecurityLevel ePset_Space | Public | |
| WinterTemperatureMin ePset_SpaceRequirement | 16 | °C |
| WinterTemperatureMax ePset_SpaceRequirement | 22 | °C |
| SummerTemperatureMin ePset_SpaceRequirement | 20 | °C |
| SummerTemperatureMax ePset_SpaceRequirement | 28 | °C |
| RequiredIlluminance ePset_SpaceRequirement | 200 | lx |
| PeakOccupancy ePset_SpaceRequirement | 10 | Personen |
| DailyOperatingHours ePset_SpaceRequirement | 12 | h/Tag |
| OutdoorAirFlowRate ePset_SpaceRequirement | 300 | m³/h |
Équipement
Prise
|
min. 1, 1 pour 10 m² de surface nette de plancher |
Interrupteur d'éclairage
|
1 |